beautypg.com

Emerson Process Management ControlWave XFC User Manual

Page 127

background image

CI-ControlWave XFC

Appendix F / F-

25

Figure F-17 - Alarm Configuration Web Page

(Accessed from Meter Run I/O Configuration Web Page)


Alarm Limit - are set via the appropriate alarm limit point.
Deadband - dead bands represent a range just below the high limits or just above the low
limits in which the alarm variable remains in an alarm state, despite the fact that its value
no longer exceeds the alarm limit. Should the alarm variable rapidly fluctuate above and
below the alarm limit (without the use of dead band settings), the system will be flooded
with alarm messages.

F.6.3 Flow Equations


When the user pushes the Flow Equation button (on the left side of the menu) the Flow
Equation Setup Web Page that is appropriate for the meter type will appear. If the meter
type has not been configured, the screen shown for Figure F.13 will appear. A user must
then select the Meter Run Type to be used.

F.6.3.1 Orifice Flow Equation Setup

F.6.3.1.1 Differential Measurement


If the user configures the meter as a Differential Measurement type, the Flow

Equation defaults to the AGA3 (1985) equation. Users may change to the AGA3
(1992) equation by toggling the push button labeled Click Here to select AGA3I

(1992).


F.6.3.1.2 1985 AGA3 Equation Configuration


The user must configure the inputs to the equation.

Pressure Tap - The user must select Pressure Tap type and location. The type is defined
Flange or Tap and the location is defined as Upstream or Downstream. Pressure Tap is
selected as follows:

1 DOWNSTREAM FLANGE
2 UPSTREAM FLANGE
3 DOWNSTREAM PIPE
4 UPSTREAM PIPE