beautypg.com

Term. plate term block – Emerson Process Management ControlWave XFC User Manual

Page 65

background image

CI-ControlWave XFC

Installation & Operation / 2-23

2.3.5 Connection to a Model 3808 Transmitter


A Model 3808 Transmitter (Digital) can be interfaced to a ControlWave XFC via either an
RS-232 or an RS-485 communication scheme. Communication schemes and cable lengths
are determined the type of communication port utilized. In general RS-232 communications
are utilized when the Model 3808 Transmitter is situated within 25 feet of the
ControlWave XFC, i.e., for local communications. Communications can be achieved with
transmitters up to 4000 feet away (remote communications) via the RS-485 scheme.

Term. Plate

Term Block

To

GND

To

RXD

To

TXD

RS-232

RS-232

3808

POWER

Notes:

Loop Wires = AWG 24

Cable Wires = AWG 22

(COM2)

10 = RTS

11 = CTS

12 = DTR
13 = DCD

To V-

8

14

RXD

RTS
CTS

DTR

DCD

TXD

G

NE

T

W

O

RK

14 = GND

8 = TXD

To R

To +

To

9 = RXD

To T

TR-

TR+

G

+V

RS4

85

J2

1 = PWR

4 = PWR+

Figure 2-13 - Model 3808 Transmitter to CW XFC - RS-232 Comm. Cable Diagram

Notes:

Loop Wires = AWG 24

Cable Wires = AWG 22

(COM3)

RS-485

To +

3 = TR+

To -

2 = TR-

Term. Plate

Term Block

To + Power

Power

To

TR-

TR+

G

+V

RS

48

5

J2

1 = PWR

4 = PWR+

To

TX/RX

(+)

To

TX/RX

(-)

RS-485

Figure 2-14 - Model 3808 Transmitter to CW XFC - RS-485 Comm. Cable Diagram