4-4 / Specifications

CI-ControlWave XFC

4-20mA Output
Compliance:

375 ohm load with Internal Power Source

45 ohm/volt load with Power Source up tp 30Vdc

General AI/AO Circuitry Specs.


Accuracy: Analog

Input

±0.1% of Span @ +25ºC (+77ºF)

±0.3% of Span @ -40ºC to +80ºC (-40ºF to 176ºF)


Analog

Output

Current Output:
±0.1% of Span @ +25ºC (+77ºF)

±0.2% of Span @ -20ºC to +70ºC (-4ºF to 158ºF)

±0.3% of Span @ -40ºC to +80ºC (-40ºF to 176ºF)

4.4.5 Non-isolated High Speed Counter Input Circuitry Specs.


Number of Inputs:

2 HSC Inputs per Module


Input Configuration:

Internally Sourced Dry Contact


Input Frequency:

10kHz Max.


Input filtering:

20 microseconds


‘1’ State Voltage:

above 1.5V


‘0’ State Voltage:

below 1.5V


Electrical isolation:

None

Surge Suppression:

Transorb between signal and ground (Meets ANSI/IEEE
C37.90-1978)

4.4.6 Function Module Terminal Plate Connectors

(see Tables 4-4 & 4-5)

Table 4-4 - User Connector Summary

Ref.

# Pins

Function

J2 14-pin Communication

Ports Intf. Connector

J3

3-pin

RTD Interface Connector

J4

11-pin

Analog I/O Interface Connector

J5 12-pin Digital I/O & High Speed Counter Intf.

Connector

J6

2-pin

Main Power Intf. Connector

4.5 TERMINAL PLATE SPECIFICATIONS

Comm. Wiring::

Pluggable Term Block, maximum wire size is 16 gauge


I/O Wiring:

Pluggable Term Block, maximum wire size is 14 gauge