Emerson Process Management ControlWave XFC User Manual
Page 92
4-4 / Specifications
CI-ControlWave XFC
4-20mA Output
Compliance:
375 ohm load with Internal Power Source
45 ohm/volt load with Power Source up tp 30Vdc
General AI/AO Circuitry Specs.
Accuracy: Analog
Input
±0.1% of Span @ +25ºC (+77ºF)
±0.3% of Span @ -40ºC to +80ºC (-40ºF to 176ºF)
Analog
Output
Current Output:
±0.1% of Span @ +25ºC (+77ºF)
±0.2% of Span @ -20ºC to +70ºC (-4ºF to 158ºF)
±0.3% of Span @ -40ºC to +80ºC (-40ºF to 176ºF)
4.4.5 Non-isolated High Speed Counter Input Circuitry Specs.
Number of Inputs:
2 HSC Inputs per Module
Input Configuration:
Internally Sourced Dry Contact
Input Frequency:
10kHz Max.
Input filtering:
20 microseconds
‘1’ State Voltage:
above 1.5V
‘0’ State Voltage:
below 1.5V
Electrical isolation:
None
Surge Suppression:
Transorb between signal and ground (Meets ANSI/IEEE
C37.90-1978)
4.4.6 Function Module Terminal Plate Connectors
(see Tables 4-4 & 4-5)
Table 4-4 - User Connector Summary
Ref.
# Pins
Function
J2 14-pin Communication
Ports Intf. Connector
J3
3-pin
RTD Interface Connector
J4
11-pin
Analog I/O Interface Connector
J5 12-pin Digital I/O & High Speed Counter Intf.
Connector
J6
2-pin
Main Power Intf. Connector
4.5 TERMINAL PLATE SPECIFICATIONS
Comm. Wiring::
Pluggable Term Block, maximum wire size is 16 gauge
I/O Wiring:
Pluggable Term Block, maximum wire size is 14 gauge