27

Fr - Reynolds Number Factor

Y - Expansion Factor

Fpb - Pressure Base Factor

Ftb - Temperature Base Factor

Ftf - Flowing Temperature Facture

Fg - Specific Gravity Factor

Extension - Square Feet of the Product of Differential Pressure and Static Pressure

F.6.3.1.3 1992 AGA3 Equation Configuration

The user must configure the inputs to the equation.

Pressure Tap - The user must toggle between pressure tap settings Flange/Upstrm and
Flange/Dnstrm.

Low Flow Cut Off - When the differential pressure drops below the low flow cut off value,
the flow rate will be set to zero. Default units are inches of water (H

2

O).

Figure F-18B - (1992 AGA3) Orifice Flow Equation Setup Web Page


Orifice Diameter - Orifice diameter is entered here. Default units are inches.

Pipe Diameter - Diameter of the pipe is entered here. Default units are inches.

Orifice Temp. Coefficient - Orifice coefficient of thermal expansion is entered here
(Inches per Inch-degree F).