Emerson Process Management ControlWave XFC User Manual

Page 180

background image

S1400CW

Page 5-2

Section 5 - Wiring Techniques

Figure 5-1 - Field Wired Circuits With & Without A Common Return

5.2.2 Use of Twisted Shielded Pair Wiring (with Overall Insulation)


For all field I/O wiring the use of twisted shielded pairs with overall insulation is highly
recommended. This type of cable provides discrete insulation for each of the wires and an
additional overall insulated covering that provides greater E.M.I. immunity and protection
to the shield as well.