beautypg.com

3 on-delay timer (ton): counting unit: 0.01 second – Yaskawa MP900 Series Motion Programming Manual User Manual

Page 192

background image

MP2300S/MP2400 Exclusive-use Commands

6.1.3 ON-DELAY TIMER (TON): Counting unit: 0.01 second

6 -6

6.1.3 ON-DELAY TIMER (TON): Counting unit: 0.01 second

Use in a sequence program

Possible

Use in a motion program

Not possible

J

Overview

The TON command counts the milliseconds (in units of 10 ms) when the bit input is ON. When
the counted value is equal to the set value, the bit output will turn ON. If the bit input turns
OFF during counting, the timer operation will stop. After the bit input turns ON again, count-
ing starts again from the beginning (0). In the registers for counting, the actual count (in units
of 10 ms) is stored.

J

Description

The TON command is designated as follows:

DB000001 = DB000000 & TON (set value DW00001);

A

B

C

D

Symbol

Application

Usable Register

A

Bit output

Bit register

(excluding # and C registers)

B

Bit input

All bit registers

C

Set value

All integer registers

Constants (0 to 65535

(655.35S): Every 10 ms)

D

Register for timer

counting

All integer registers

S

Milliseconds are not counted while the debugging operation is stopped.
Counting starts again from the current counted value after the debugging operation restarts.

S

Be sure to designate bit input “DBxxxxxx&.”

6

6

IMPORTANT

This manual is related to the following products: