Flowchart A: Basic Start-up and Motor Tuning

Figure 4.4

, Flowchart A, describes basic start-up sequence for the drive and motor system.

This sequence varies slightly depending on application. Use drive default parameter settings

in simple applications that do not require high precision.

Install and wire the drive as explained in Chapters 1, 2, and 3

START

Apply main power on to the drive

Adhere to safety messages concerning application of power

Application Presets

A1-06 used ?

No

Set the control mode in parameter A1-02.

Set the basic parameters

Refer to
Application
Selection section

To

To

Flowchart A-1

Control Mode

A1-02 =

0: V/f control

5: Open Loop Vector for PM motors

2: Open Loop
Vector control

To

Flowchart A-2

Flowchart A-3

* b1-01/02 for frequency reference and run command source selection
* H1-,H2-,H3-,H4-,H6- for I/O terminal setting
* d1- for multi-speed references if used
* C1- and C2-
* C6-01 for heavy/normal duty mode selection
* L3-04 if braking options are used

for accel./decel. and S-curve time settings

Run the motor without load; check the rotation direction and operation.

Verify external signal commands to the drive work as desired.

Couple the load or machine to the motor. Run the machine and check for desired operation.

Fine tune parameters. Adjust application settings (PID, ...) if necessary.

Check the machine operation and verify parameter settings.

Drive is ready to run the application.

From Flowchart A-1, A-2, or A-3

Yes

TO

FROM

Figure 4.4 Basic Start-up and Motor Tuning