No.

Name

Description

L3-20

Main Power Circuit Voltage

Adjustment Gain

Refer to V1000 Technical Manual for details.

L3-21

Accel/Decel Rate Calculation Gain Refer to V1000 Technical Manual for details.

L3-22

Deceleration Time at Stall

Prevention during Acceleration

Refer to V1000 Technical Manual for details.

L3-23

Automatic Reduction Selection for

Stall Prevention during Run

0: Sets the stall prevention level throughout the entire frequency range

to the value in parameter L3-06.

1: Automatically lowers the stall prevention level in the constant output

range. The lower limit value is 40% of L3-06.

L3-24

Motor Acceleration Time for

Inertia Calculations

Refer to V1000 Technical Manual for details.

L3-25

Load Inertia Ratio

Refer to V1000 Technical Manual for details.

L4: Frequency Detection

Use L4 parameters to configure frequency detection operation.

L4-01

Speed Agreement Detection

Level

These parameters configure the multi-function output (H2- = 2, 3,

4, 5) settings “Fref/Fout Agree 1,” “Fref/Set Agree 1,” “Frequency

Detection 1,” and “Frequency detection 2.”

L4-02

Speed Agreement Detection Width

L4-03

Speed Agreement Detection Level

(+/-)

Refer to V1000 Technical Manual for details.

L4-04

Speed Agreement Detection Width

(+/-)

L4-05

Frequency Reference Loss

Detection Selection

0: Stop - Drive will stop

1: Run at L4-06

L4-06

Frequency Reference at Reference

Loss

Refer to V1000 Technical Manual for details.

L4-07

Frequency Detection Conditions

Refer to V1000 Technical Manual for details.

L4-08

Speed Agreement Detection

Conditions

Refer to V1000 Technical Manual for details.

Note: Available in drive software versions PRG: 1016 and later.

L5: Fault Reset

Use L5 parameters to configure Automatic Restart after fault.

L5-01

Number of Auto Restart

Attempts

Sets the counter for the number of times the drive attempts to restart

when the following faults occur: GF, LF, oC, oH1, ov, PF, rH, rr, oL1,

oL2, oL3, oL4, STo, Uv1.

L5-02

Auto Restart Operation Selection Refer to V1000 Technical Manual for details.

L5-04

Fault Reset Interval Time

Refer to V1000 Technical Manual for details.

L5-05

Fault Reset Operation Selection

Refer to V1000 Technical Manual for details.

L6: Overtorque Detection

Use L6 parameters to configure overtorque detection.

B.1 Parameter Table

200

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide