A.4 drive specifications – Yaskawa J1000 Compact Vector Control Drive User Manual
Page 172

Item
Specification
Environment
Storage/Installation Area
Indoors
Ambient Temperature
IP20/NEMA Type 1 enclosure: -10 °C to +40 °C (14 °F to 104 °F)
IP20/IP00 Open-Chassis enclosure: -10 °C to +50 °C (14 °F to 122 °F)
Finless Type: IP20/IP00 enclosure: -10 °C to +50 °C (14 °F to 122 °F)
NEMA Type 4X/IP66 enclosure: -10 °C to +40 °C (14 °F to 104 °F)
Humidity
95% RH or less with no condensation
Storage Temperature
-20 to +60 °C (-4 to +140 °F) allowed for short-term transport of the
product
Altitude
Up to 1000 meters without derating; up to 3000 meters with output
current and voltage derating.
Shock, Impact
10 to 20 Hz: 9.8 m/s
2
20 to 55 Hz: 5.9 m/s
2
Surrounding Area
Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water or other foreign materials
• radioactive materials
• combustible materials
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight
Orientation
Install the drive vertically to maintain maximum cooling effects
Standards
• UL508C
• EN 61800-3:2004/A1:2012, IEC/EN 61800-5-1
• ISO/EN 13849-1 Cat.3 PLd, IEC/EN 61508 SIL2
Time from input open to drive output stop is less than 1 ms.
Protective Enclosure
IP20/Open-Chassis or IP00/Open-Chassis
<8>
IP20/NEMA Type 1
<9>
Cooling Method
BA0001 to BA0006: self-cooled
BA0010 to BA0018: cooling fan
2A0001 to 2A0004: self-cooled
2A0006 to 2A0069: cooling fan
4A0001 to 4A0004: self-cooled
4A0005 to 4A0038: cooling fan
<1>
Speed control accuracy varies somewhat according to the type of motor and drive settings.
<2>
Instantaneous average deceleration torque refers to the torque required to decelerate the motor (uncoupled from
the load) from the rated motor speed down to zero in the shortest time.
<3>
Ensure that Stall Prevention Selection during Deceleration is disabled (L3-04 = 0) or set to 3 when using a
braking resistor or the Braking Resistor Unit. The default setting for the stall prevention function will interfere
with the braking resistor.
<4>
Overload protection may be triggered when operating with 150% of the rated output current if the output
frequency is less than 6 Hz.
<5>
Parameter settings allow up to 150 V.
A.4 Drive Specifications
172