• Auto-Tuning is not possible with permanent magnet motors.
• To cancel Auto-Tuning, press the STOP key on the LED operator.

Table 4.19

describes digital input and output terminal status during Auto-Tuning.

Table 4.19 Digital Input and Output Operation During Auto-Tuning

Auto-Tuning Type

Digital Input

Digital Output

Rotational Auto-Tuning for V/f Control

Not available

Functions the same as during normal operation

Rotational Auto-Tuning for OLV Control

Not available

Functions the same as during normal operation

Stationary Auto-Tuning for Line-to-Line

Resistance

Not available

Maintains the status at the start of Auto-Tuning

WARNING! Sudden Movement Hazard. Do not release the mechanical brake during stationary Auto-Tuning.

Inadvertent brake release may cause damage to equipment or injury to personnel. Ensure that the mechanical

brake release circuit is not controlled by the drive multi-function digital outputs.

Note:

It is recommended that Rotational Auto-Tuning is performed with the load disconnected. Failure to

comply could result in improper drive operation. If Rotational Auto-Tuning is performed for a motor

coupled to a load, the motor constants will be inaccurate and the motor may exhibit abnormal operation.

Disconnect or decouple the motor from the load.

n

Notes on Rotational Auto-Tuning

• For optimal performance, Auto-Tuning should only be done with the motor uncoupled from

the load for applications requiring high performance over a wide speed range.

• If motor and load cannot be uncoupled, the load should be lower than 30% of the rated load.

Performing Rotational Auto-Tuning with a higher load will set motor parameters

incorrectly, and can cause irregular motor rotation.

• Ensure the motor-mounted brake is fully released if installed.
• Connected machinery should be allowed to rotate the motor.

n

Notes on Stationary Auto-Tuning for Terminal Resistance Only

• If the motor cable lead length has been significantly modified after Auto-Tuning has already

been performed, perform Stationary Auto-Tuning with the new cables.

• Perform when using motor cables longer than 50 m with V/f Control.

WARNING! Electrical Shock Hazard. When executing stationary Auto-Tuning for line-to-line resistance only,

the motor does not rotate, however, power is applied. Do not touch the motor until Auto-Tuning is completed.

Failure to comply may result in injury from electrical shock.

4.7 Auto-Tuning

114

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide