H1 Multi-Function Digital Input Selections

H1-

Setting

Function

Description

9F

DriveWorksEZ enable

Open: DWEZ enabled

Closed: DWEZ disabled

No.

Name

Description

Range

H2: Multi-Function Digital Outputs

Use H2 parameters to assign functions to the multi-function digital outputs.

H2-01 Terminal MA, MB and MC Function Selection (relay)

Refer to “Multi-Function Digital

Output Selection Table” for a

description of setting values.

0 to 192

H2-02 Terminal P1 Function Selection (open-collector)
H2-03 Terminal P2 Function Selection (open-collector)
H2-06 Watt Hour Output Unit Selection

Refer to V1000 Tech Manual.

0 to 4

H2 Multi-Function Digital Output Settings

H2-

Setting

Function

Description

0

During Run

Closed: A Run command is active or voltage is output.

1

Zero Speed

Closed: Output frequency is 0.

2

Speed Agree 1

Closed: Output frequency equals the speed reference (plus or minus the

hysteresis set to L4-02).

3

User Set Speed Agree 1

Closed: Output frequency and speed reference equal the value in L4-01

(plus or minus the hysteresis of L4-02).

4

Frequency Detection 1

Closed: Output frequency is less than or equal to the value in L4-01 with

hysteresis determined by L4-02.

5

Frequency Detection 2

Closed: Output frequency is greater than or equal to the value in L4-01,

with hysteresis determined by L4-02.

6

Drive Ready

Closed: Drive Ready. The drive is powered up, not in a fault state, and

in the Drive mode.

7

DC Bus Undervoltage

Closed: DC bus voltage is below the UV trip level set in L2-05.

8

During Baseblock (N.O.)

Closed: This is no output voltage

9

Frequency Reference Source

Closed: Digital operator supplies the frequency reference.

A

Run Command Source

Open: Reference 1 or 2 are active

Closed: Digital operator supplies the run command.

B

Torque Detection 1 (N.O.)

Closed: Output current/torque exceeds the torque value set in parameter

L6-02 for longer than the time set in parameter L6-03.

C

Frequency Reference Loss

Closed: Loss of the analog frequency reference detected. Enabled when

L4-05 = 1.

D

Braking Resistor Fault

Closed: Braking resistor or transistor is overheated or faulted out.

E

Fault

Closed: Fault occurred (other than CPF00 and CPF01).

F

Not used/Through Mode

Set this value when the terminal is not used, or when using the terminal

in the pass-through mode.

B.1 Parameter Table

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide

193

B

Parameter List