A.3 three-phase 400 v class drives – Yaskawa J1000 Compact Vector Control Drive User Manual
Page 169

Table A.5 Power Ratings Continued
Item
Specification
Three-Phase Model
4A0011
4A0018
4A0023
4A0031
4A0038
Maximum Applicable Motor
Capacity (HP)
<1>
ND Rating
7.5
10.0
15.0
20.0
25.0
HD Rating
5.0
10.0
10.0
15.0
20.0
Input
Input Current (A)
<2>
ND Rating
14.0
20.0
24.0
38.0
44.0
HD Rating
10.4
15.0
20.0
29.0
39.0
Output
Output Current (kVA)
<3>
ND Rating
<4>
8.5
13.3
17.5
23.6
29.0
HD Rating
<5>
7.0
11.3
13.7
18.3
23.6
Output Current (A)
ND Rating
<4>
11.1
17.5
23.0
31.0
38.0
HD Rating
<5>
9.2
14.8
18.0
24.0
31.0
Overload Tolerance
ND Rating: 120% of rated output current for 60 s
HD Rating: 150% of rated output current for 60 s
(Derating may be required for applications that start and stop
frequently)
Carrier Frequency
User-adjustable 2 to 15 kHz
Max Output Voltage (V)
Three-phase power: 380 to 480 V (proportional to input voltage)
Max Output Frequency (Hz)
400 Hz (user-adjustable)
Power
Supply
Rated Voltage
Rated Frequency
Three-phase power: 380 to 480 V 50/60 Hz
DC power supply: 510 to 680 V
<6>
Allowable Voltage Fluctuation
-15 to 10%
Allowable Frequency Fluctuation
±5%
Harmonic Corrective Actions DC Link Choke
Optional
<1>
The motor capacity (HP) refers to a NEC 4-pole motor. The rated output current of the drive output amps should
be equal to or greater than the motor rated current.
<2>
Input current rating varies depending on the power supply transformer, input reactor, wiring conditions, and
power supply impedance.
<3>
Rated motor capacity is calculated with a rated output voltage of 440 V.
<4>
Carrier frequency is set to 2 kHz (Swing PWM). Current derating is required to raise the carrier frequency.
<5>
Carrier frequency is set to 8 kHz. Current derating is required to raise the carrier frequency.
<6>
DC is not available for UL standards.
A.3 Three-Phase 400 V Class Drives
YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide
169
A
Specifications