beautypg.com

Low voltage wiring for control circuit terminals, C.2 ul and csa standards – Yaskawa J1000 Compact Vector Control Drive User Manual

Page 230

background image

Drive

Model

Non-time

Delay

Fuse Rating

(A)

<1>

Time Delay Fuses

Bussmann

Semiconductor

Fuse Part Number

(Fuse Ampere)

<4>

MCCB

<5>

Class J, T,

or CC

Fuse Rating

(A)

<2>

Class RK5

Fuse Rating

(A)

<3>

Rating (A)

Minimum

Enclosure

Volume (in

3

)

4A0018

35

45

FWH-80B (80)

50

1152

4A0023

40

50

FWH-100B (100)

60

1152

4A0031

60

80

FWH-125B (125)

90

1152

4A0038

70

90

FWH-200B (200)

110

1152

<1>

Maximum 300% of drive input current rating for any Class J, T, or CC fuse except for models 2A0002, 2A0004,
4A0004, 4A0005, and 4A0007.

<2>

Maximum 175% of drive input current rating for any Class J, T, or CC fuse.

<3>

Maximum 225% of drive input current rating for any Class RK5 fuse.

<4>

When using semiconductor fuses, Bussmann FWH are required for UL compliance.

<5>

Maximum MCCB Rating is 15 A or 200% of drive input current rating, whichever is larger. MCCB voltage
rating must be 600 Vac or greater. Additionally, when using MCCBs for protection, the drive must be installed
in a ventilated enclosure with minimum volume according the “Minimum Enclosure Volume” column.

<6>

Model 2A0002 requires Mersen (Ferraz) part number A6T6 for compliance.

<7>

Models 2A0004 and 4A0004 require Mersen (Ferraz) part number A6T15 for compliance.

<8>

Model 4A0005 requires Mersen (Ferraz) part number A6T20 for compliance.

<9>

Model 4A0007 requires Mersen (Ferraz) part number A6T25 for compliance.

n

Low Voltage Wiring for Control Circuit Terminals

Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local

codes for wiring. The external power supply shall be a UL-Listed Class 2 power source or

equivalent.

Table C.11 Control Circuit Terminal Power Supply

Input / Output

Terminal Signal

Power Supply Specifications

Multi-function photocoupler

output

P1, P2, PC

Requires class 2 power supply

Multi-function digital inputs

S1, S2, S3, S4, S5, S6, S7, SC

Use the internal power supply of the drive.

Use class 2 for external power supply.

Multi-function analog inputs

A1, A2, AC

Use the internal power supply of the drive.

Use class 2 for external power supply.

Pulse train input

RP

Use the internal LVLC power supply of the

drive. Use class 2 for external power supply.

Pulse train output

MP

Use the internal LVLC power supply of the

drive. Use class 2 for external power supply.

C.2 UL and CSA Standards

230

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide