A.4 drive specifications – Yaskawa J1000 Compact Vector Control Drive User Manual
Page 171

Item
Specification
Control
Character-
istics
Functions
Momentary Power Loss Ride-Thru
Speed Search
Over/Undertorque Detection
Torque Limit, Multi-Step Speed (17 steps max)
Accel/Decel Time Switch
S-Curve Accel/Decel,
2-Wire/3-Wire Sequence
Rotational Auto-Tuning
Stationary Auto-Tuning of Line-to-Line Resistance
Dwell
Cooling Fan ON/OFF
Slip Compensation
Torque Compensation
Jump Frequencies (reference dead band)
Frequency Reference Upper/Lower Limit
DC Injection Braking (start and stop), High Slip Braking
PID Control (with Sleep Function)
Energy Saving
MEMOBUS/Modbus (RS-485/RS-422 Max 115.2 kbps)
Fault Reset
Parameter Copy
DriveWorksEZ
Fault Restart
Removable Terminals with Parameter Backup Function
Protection
Functions
Motor Protection
Motor overheat protection via output current sensor
Overcurrent Protection
Drives stops when output exceeds 200% of the rated current (Heavy
Duty)
Overload Protection
A stop command will be entered after operating at 150% for 60 s
(Heavy Duty)
<4>
Overvoltage Specification
200 V Class: Stops when DC bus voltage exceeds approx. 410 V
400 V Class: Stops when DC bus voltage exceeds approx. 820 V
Low Voltage Protection
Drive stops when DC bus voltage falls below the levels indicated:
<5>
190 V (3-phase 200 V), 160 V (single-phase 200 V), 380 V (3-phase
400 V), 350 V (3-phase 380 V)
Momentary Power Loss Ride-
Thru
3 selections available: Ride-Thru disabled (stops after 15 ms), time base
of 0.5 s, and continue running as long as the drive control board is
powered up.
<6>
Heatsink Overheat Protection
Protected by thermistor
Braking Resistor Overheat
Protection
Overheat input signal for braking resistor (Optional ERF-type, 3% ED)
Stall Prevention
Stall prevention is available during acceleration, deceleration, and
during run. Separate settings for each type of stall prevention determine
the current level at which stall prevention is triggered.
Cooling Fan Failure Protection
Circuit protection (“fan-lock” sensor)
Ground Fault Protection
Electronic circuit protection
<7>
DC Bus Charge LED
Remains lit until DC bus voltage falls below 50 V
A.4 Drive Specifications
YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide
171
A
Specifications