H1: Multi-Function Digital Input

H1 parameters to assign functions to the multi-function digital input terminals. Unused terminals should be set to “F”.

H1-01 Multi-Function Digital Input Terminal S1 Function Selection Selects function of terminal S1
H1-02 Multi-Function Digital Input Terminal S2 Function Selection Selects function of terminal S2
H1-03 Multi-Function Digital Input Terminal S3 Function Selection Selects function of terminal S3
H1-04 Multi-Function Digital Input Terminal S4 Function Selection Selects function of terminal S4
H1-05 Multi-Function Digital Input Terminal S5 Function Selection Selects function of terminal S5
H1-06 Multi-Function Digital Input Terminal S6 Function Selection Selects function of terminal S6
H1-07 Multi-Function Digital Input Terminal S7 Function Selection Selects function of terminal S7

H1 Multi-Function Digital Input Selections

H1-

Setting

Function

Description

0

3-Wire Sequence

Closed: Reverse rotation (only for 3-wire sequence)

1

Local/Remote Selection

Open: Remote, Reference 1 or 2 (b1-01/02 or b1-15/16)

Closed: Local, LED operator is run and reference source

2

External Reference 1/2

Open: Run and frequency reference source 1 (b1-01/02)

Closed: Run and frequency reference source 2 (b1-01/02)

3

Multi-Step Speed Reference 1

Used to select Multi-Step Speeds set in d1-01 to d1-16

4

Multi-Step Speed Reference 2

5

Multi-Step Speed Reference 3

6

Jog Reference Selection

Open: Selected speed reference

Closed: Jog Frequency reference (d1-17). Jog has priority over all other

reference sources.

7

Accel/Decel Time 1

Used to switch between Accel/Decel. Time 1/2

8

Baseblock Command (N.O.)

Open: Normal operation

Closed: No drive output

9

Baseblock Command (N.C.)

Open: No drive output

Closed: Normal operation

A

Accel/Decel Ramp Hold

Closed: The drive pauses during acceleration or deceleration and maintains

the output frequency.

B

Drive Overheat Alarm (oH2)

Closed: Closes when an oH2 alarm occurs.

C

Terminal A1/A2 Enable

Terminal status differs depending on drive software version.

PRG: 1016 and later:

Open: Analog input selected by H3-14 is disabled.

Closed: Analog input selected by H3-14 is enabled.

PRG: 1015 and earlier:

Open: Analog inputs selected for terminals A1 and A2 are disabled.

Closed: Analog inputs selected for terminals A1 and A2 are enabled.

F

Not used

Select this setting when not using the terminal or when using the terminal

in a pass-through mode.