background image

No.

Parameter Name

Default Setting

H2-03

Terminals P2 Function Selection

5: Frequency Detection 2

L2-03

Momentary Power Loss Minimum

Baseblock Time

0.3 s

L3-04

Momentary Power Loss Voltage Recovery

Ramp Time

0: Disabled

L4-01

Speed Agreement Detection Level

2.0 Hz

L4-02

Speed Agreement Detection Width

0.0 Hz

L6-01

Torque Detection Selection 1

8: UL3 at RUN - Fault

L6-02

Torque Detection Level 1

5%

L6-03

Torque Detection Time 1

0.5 s

L8-05

Input Phase Loss Protection Selection

1: Enabled

<1>

L8-07

Output Phase Loss Protection Selection

1: Enabled

L8-38

Carrier Frequency Reduction

1: Enabled below 6 Hz

L8-41

High Current Alarm Selection

1: Enabled (alarm is output)

<1>

Disable L8-05 for single-phase models.

Table 4.14 Preset 6: User Parameters (A2-01 to A2-16):

No.

Parameter Name

No.

Parameter Name

A1-02 Control Method Selection

d1-02

Frequency Reference 2

b1-01

Frequency Reference Selection 1

d1-03

Frequency Reference 3

b6-01

Dwell Reference at Start

E1-08 Middle Output Frequency Voltage

b6-02

Dwell Time at Start

H2-01 Terminals MA, MB, and MC Function

Selection

C1-01 Acceleration Time 1

L1-01 Motor Overload Protection Selection

C1-02 Deceleration Time 1

L4-01 Speed Agreement Detection Level

C6-02 Carrier Frequency Selection

L6-02 Torque Detection Level 1

d1-01

Frequency Reference 1

L6-03 Torque Detection Time 1

u

Notes on Controlling the Brake when Using Application
Preset 6

The frequency detection function is used for controlling the brake.
When an external Baseblock command is present while a Run command is active, the

frequency reference will be kept as long as the Run command is active. To avoid improper

brake operation make sure that frequency detection is set so that the brake does not open during

Baseblock (L4-07 = “0”, default).

4.5 Application Selection

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide

101

4

Start-Up Programming & Operation