B.1 parameter table – Yaskawa J1000 Compact Vector Control Drive User Manual
Page 194

H2 Multi-Function Digital Output Settings
H2-
Setting
Function
Description
10
Alarm
Closed: An alarm is triggered.
11
Reset Command Active
Closed: The drive has received a reset command from the multi-function
input terminals or from serial network, or the digital operator RESET
key has been pressed.
12
Timer Output
Timer output, controlled by b4-01 and b4-02. Used in conjunction with
the digital input (H1- = 18 “timer function”).
13
Speed Agree 2
Closed: When drive output frequency equals the frequency reference +/-
L4-04.
14
User Set Speed Agree 2
Closed: When the drive output frequency is equal to the value in L4-03
(plus or minus L4-04).
15
Frequency Detection 3
Closed: When the drive output frequency is less than or equal to the value
in L4-03 with the hysteresis determined by L4-04.
16
Frequency Detection 4
Closed: When the output frequency is greater than or equal to the value
in L4-03 with the hysteresis determined by L4-04.
17
Torque Detection 1 (N.C.)
Open: When the output current/torque exceeds the value set in parameter
L6-02 for more time than is set in parameter L6-03.
18
Torque Detection 2 (N.O.)
Closed: When the output current/torque exceeds the value set in
parameter L6-05 for more time than is set in parameter L6-06.
19
Torque Detection 2 (N.C.)
Open: Output current/torque exceeds the value set in parameter L6-05
for more time than is set in parameter L6-06.
1A
During Reverse Operation
Closed: Drive is running in the reverse direction.
1B
During Baseblock (N.C.)
Open: Drive is in base block condition. Output is disabled.
1C
Motor 2 Selection
Closed: Motor 2 is selected by a digital input (H1- = 16)
1E
Restart Enabled
Closed: An automatic restart is performed
1F
Motor Overload Alarm (oL1)
Closed: OL1 is at 90% of its trip point or greater.
20
Drive Overheat Pre-alarm (oH)
Closed: Heatsink temperature exceeds the parameter L8-02 value.
22
Mechanical Weakening
Closed: Mechanical Weakening detected.
2F
Maintenance Period
Closed: cooling fan, electrolytic capacitors, IGBTs, or the soft charge
bypass relay may require maintenance.
Note: Available in drive software versions PRG: 1016 and later.
30
During Torque Limit
Closed: When the torque limit has been reached.
37
During Frequency Output
Open: No frequency output from drive if stopped, with baseblock, with
DC injection braking during initial excitation, or with short-circuit
braking.
Closed: Drive is outputting a frequency
38
Drive Enable
Closed: Multi-function input closes (H1- = 6A)
39
Watt Hour Pulse Output
Output units are determined by H2-06, outputs 200 ms pulse for each
incremented kWh count.
3C
LOCAL/REMOTE Status
Closed: LOCAL
Open: REMOTE
B.1 Parameter Table
194
YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide