Table c.10, Molded case circuit breakers (mccb), C.2 ul and csa standards – Yaskawa J1000 Compact Vector Control Drive User Manual
Page 229

• Molded Case Circuit Breakers (MCCB).
Table C.10 Factory Recommended Drive Branch Circuit Protection
Drive
Model
Non-time
Delay
Fuse Rating
(A)
<1>
Time Delay Fuses
Bussmann
Semiconductor
Fuse Part Number
(Fuse Ampere)
<4>
MCCB
<5>
Class J, T,
or CC
Fuse Rating
(A)
<2>
Class RK5
Fuse Rating
(A)
<3>
Rating (A)
Minimum
Enclosure
Volume (in
3
)
200 V Class Single-Phase Drives
BA0001
6
3.5
4
FWH-25A14F (25)
15
600
BA0002
10
6
8
FWH-25A14F (25)
15
600
BA0003
20
10
15
FWH-60B (60)
15
600
BA0006
40
20
30
FWH-80B (80)
30
1152
BA0010
40
35
45
FWH-100B (100)
50
1152
BA0012
50
40
50
FWH-125B (125)
60
1152
BA0018
80
60
70
FWH-175B (175)
80
1152
200 V Class Three-Phase Drives
2A0001
3
1.5
2
FWH-25A14F (25)
15
600
2A0002
6
<6>
3
3
FWH-25A14F (25)
15
600
2A0004
15
<7>
6
8
FWH-25A14F (25)
15
600
2A0006
20
10
15
FWH-25A14F (25)
15
1152
2A0010
25
15
20
FWH-70B (70)
25
1152
2A0012
25
20
30
FWH-70B (70)
30
1152
2A0020
40
40
50
FWH-90B (90)
60
1152
2A0030
–
60
80
FWH-100B (100)
90
1152
2A0040
–
90
110
FWH-200B (200)
125
1152
2A0056
–
110
150
FWH-200B (200)
150
2560
2A0069
–
125
175
FWH-200B (200)
200
2560
400 V Class Three-Phase Drives
4A0001
3
2
2
FWH-40B (40)
15
1152
4A0002
6
3.5
3
FWH-40B (40)
15
1152
4A0004
15
<7>
7
8
FWH-50B (50)
15
1152
4A0005
20
<8>
10
10
FWH-70B (70)
15
1152
4A0007
25
<9>
12
15
FWH-70B (70)
20
1152
4A0009
25
15
20
FWH-90B (90)
20
1152
4A0011
30
20
30
FWH-90B (90)
35
1152
C.2 UL and CSA Standards
YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide
229
C
Standards Compliance