Wire size and torque specifications, Ferrule-type wire terminations, 5 control circuit wiring – Yaskawa J1000 Compact Vector Control Drive User Manual
Page 71

n
Wire Size and Torque Specifications
Select appropriate wire type and size from
. For simpler and more reliable wiring,
crimp ferrules to the wire ends. Refer to
for ferrule terminal types and sizes.
Table 3.9 Wire Size and Torque Specifications (Same for All Models)
Terminal
Screw
Size
Tightening
Torque
N•m
(in-lbs)
Bare Wire Terminal
Ferrule-Type Terminal
Applic. wire
size
mm
2
(AWG)
Recomm.
mm
2
(AWG)
Applic. wire
size
mm
2
(AWG)
Recomm.
mm
2
(AWG)
Wire
Type
MA, MB,
MC
M3
0.5 to 0.6
(4.4 to 5.3)
Stranded: 0.25
to 1.5
(24 to 16)
Single: 0.25 to
1.5
(24 to 16)
0.75 (18)
0.25 to 1.0
(24 to 17)
0.5 (20)
Shielded
line, etc.
S1-S7, SC,
RP, +V, A1,
A2, AC, HC,
H1, P1, P2,
PC, MP,
AM, AC, S
+, S-, R+, R-,
IG
M2
0.22 to 0.25
(1.9 to 2.2)
Stranded: 0.25
to 1.0
(24 to 18)
Single: 0.25 to
1.5
(24 to 16)
0.75 (18)
0.25 to 0.5
(24 to 20)
0.5 (20)
n
Ferrule-Type Wire Terminations
Crimp a ferrule to signal wiring to improve wiring simplicity and reliability. Use CRIMPFOX
6, a crimping tool manufactured by PHOENIX CONTACT.
d1
d2
6 mm
L
Figure 3.16 Ferrule Dimensions
3.5 Control Circuit Wiring
YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide
71
3
Electrical Installation