Yaskawa J1000 Compact Vector Control Drive User Manual
Page 227

Drive
Model
Terminal
Recomm.
Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening
Torque
N•m (lb.in.)
4A0018
R/L1, S/L2, T/L3
10
14 to 6
M4
2.1 to 2.3
(18.6 to 20.4)
U/T1, V/T2, W/T3
10
14 to 6
⊖, ⊕1, ⊕2
–
14 to 6
B1, B2
–
14 to 10
8
14 to 6
M5
2 to 2.5
(17.7 to 22.1)
4A0023
R/L1, S/L2, T/L3
10
10 to 6
M4
2.1 to 2.3
(18.6 to 20.4)
U/T1, V/T2, W/T3
10
10 to 6
⊖, ⊕1, ⊕2
–
10 to 6
B1, B2
–
14 to 10
8
10 to 6
M5
2 to 2.5
(17.7 to 22.1)
4A0031
R/L1, S/L2, T/L3
8
10 to 6
M5
3.6 to 4.0
(31.8 to 35.4)
U/T1, V/T2, W/T3
8
10 to 6
⊖, ⊕1, ⊕2
–
10 to 6
B1, B2
–
14 to 10
2.7 to 3.0
(23.9 to 26.6)
6
<1>
10 to 6
M6
5.4 to 6.0
(47.8 to 53.1)
4A0038
R/L1, S/L2, T/L3
6
10 to 6
M5
3.6 to 4.0
(31.8 to 35.4)
U/T1, V/T2, W/T3
8
10 to 6
⊖, ⊕1, ⊕2
–
10 to 6
B1, B2
–
10 to 8
2.7 to 3.0
(23.9 to 26.6)
6
10 to 6
M6
5.4 to 6.0
(47.8 to 53.1)
<1>
When an EMC filter is installed, additional measures must be taken to comply with IEC/EN 61800-5-1.
to EMC Filter Installation on page 216
for details.
Note:
Use crimp insulated terminals or insulated tubing for wiring these connections. Wires should have a
continuous maximum allowable temperature of 75 °C 600 V UL approved vinyl sheathed insulation.
Ambient temperature should not exceed 30 °C.
Closed-Loop Crimp Terminal Recommendations
Yaskawa recommends crimp terminals made by JST and Tokyo DIP for the insulation cap.
matches the wire gauges and terminal screw sizes with Yaskawa-recommended
crimp terminals, tools, and insulation caps. Refer to the appropriate Wire Gauge and Torque
Specifications table for the wire gauge and screw size for your drive model. Place orders with
a Yaskawa representative or the Yaskawa sales department.
C.2 UL and CSA Standards
YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide
227