B.1 parameter table – Yaskawa J1000 Compact Vector Control Drive User Manual
Page 197

No.
Name
Description
H4: Multi-Function Analog Outputs
Use H4 parameters to configure the multi-function analog output terminals.
H4-01 Multi-Function Analog Output
Terminal AM)
Selects data output via multi-function analog output terminal AM.
H4-02 Multi-Function Analog Output
Terminal AM Gain
Sets terminal AM output level when selected monitor is at 100%.
H4-03 Multi-Function Analog Output
Terminal AM Gain
Refer to V1000 Technical Manual for details.
H5: MEMOBUS/Modbus Communications
Use H5 Parameters to connect the drive to a MEMOBUS/Modbus network.
The settings for MEMOBUS/Modbus communications become effective when the drive is restarted.
H5-01 Drive Node Address
Selects drive station node number (address) for MEMOBUS/Modbus
terminals R+, R-, S+, S-. Cycle power for the setting to take effect.
H5-02 Communication Speed Selection
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
6: 57600 bps
7: 76800 bps
8: 115200 bps
H5-03 Communication Parity Selection
0: No parity
1: Even parity
2: Odd parity
H5-04 Stopping Method After
Communication Error
0: Ramp to stop
1: Coast to stop
2: Fast-stop
3: Alarm only
H5-05 Communication Fault Detection
Selection
0: Disabled
1: Enabled - If communication is lost for more than two seconds, a CE
fault will occur.
H5-06 Drive Transmit Wait Time
Set the wait time between receiving and sending data.
H5-07 RTS Control Selection
0: Disabled - RTS is always on.
1: Enabled - RTS turns on only when sending.
H5-09 CE Detection Time
Refer to V1000 Technical Manual for details.
H5-10 Unit Selection for MEMOBUS/
Modbus Register 0025H
Refer to V1000 Technical Manual for details.
H5-11 Communications ENTER
Function Selection
Refer to V1000 Technical Manual for details.
H5-12
Run Command Method Selection Refer to V1000 Technical Manual for details.
H6: Pulse Train Input/Output
Use H6 parameters to configure Pulse Train I/O operation.
B.1 Parameter Table
YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide
197