Heat dissipation, Environmental specifications, Noise – H3C Technologies H3C S10500 Series Switches User Manual
Page 77
67
Heat dissipation
Heat dissipation is measured in BTU/h, and 1 W equals 3.4121BTU/h.
The heat dissipation of a switch depends on its power consumption. To calculate heat dissipation of the
switch, assume 90% power consumption is converted to heat, and the efficiency of the power module is
90%. Heat dissipation/hour of the switch is 0.9 × (total power consumption of the cards plus power
consumption of the fan tray)/0.9 × 3.4121.
shows the heat dissipation for each switch model.
Table 19 Heat dissipation
Model Heat
dissipation (BTU/h)
S10504 5732
S10506 6957
S10508 9943
S10508-V 10267
S10510 11489
S10512 15369
For the power consumption of the cards and fan trays of the H3C S10500 Switch Series, see "
power consumption and system power consumption
Environmental specifications
Table 20 Environmental specifications
Description Operating
Non-operating
Temperature
0°C to 45°C (32°F to 113°F)
–40°C to +70°C (–40°F to +158°F)
Relative humidity
10% to 95% (non-condensing)
5% to 95% (non-condensing)
Noise
The switch uses fan trays that can adjust the fan speed automatically based on the device temperature.
The sound pressure levels vary by fan speed. For more information, see
Table 21 Sound pressure levels
Model
Sound pressure level in the
acceptable temperature range
Sound pressure level when the
fan tray operates at full speed
S10504
62.3 dBA
75.5 dBA
S10506
66.9 dBA
74.4 dBA
S10508
63 dBA
75.8 dBA
S10508-V
61.6 dBA
72.6 dBA