Table 1 Temperature requirements

Temperature Range

Operating temperature

0°C to 45°C (32°F to 113°F)

Storage temperature

–40°C to +70°C (–40°F to +158°F)

Humidity

Maintain appropriate humidity in your equipment room, as described in

Table 2

.

Lasting high relative humidity can cause poor insulation, electricity creepage, mechanical property
change of materials, and metal corrosion.

Lasting low relative humidity can cause washer contraction and ESD and cause problems including
loose mounting screws and circuit failure.

Table 2 Humidity requirements

Humidity Range

Operating humidity

10% to 95%, noncondensing

Storage humidity

5% to 95%, noncondensing

Cleanliness

Mechanically active substances buildup on the chassis might result in electrostatic adsorption, which

causes poor contact of metal components and contact points. In the worst case, electrostatic adsorption

can cause communication failure.

Table 3 Mechanically active substance concentration limit in the equipment room

Substance Particle

diameter

Concentration limit

Dust particles

≥ 5 μm

≤ 3 x 10

4

particles/m

3

(No visible dust on desk in three days)

Dust (suspension)

≤ 75 μm

≤ 0.2 mg/m

3

Dust (sedimentation) 75 μm to 150 μm

≤ 1.5 mg/(m

2

h)

Sand

≥ 150 μm

≤ 30 mg/m

3

The equipment room must also meet strict limits on salts, acids, and sulfides to eliminate corrosion and
premature aging of components, as shown in

Table 4

.

Table 4 Harmful gas limits in the equipment room

Gas

Maximum concentration (mg/m

3

)

SO

2

0.2

H

2

S 0.006

NH

3

0.05

Cl

2

0.01