SCADA Details Screen

NOTICE:

SCADA traffic has a higher priority than other types of traffic flowing
through the unit. Refer to Normal Tx Queue Size on page 3-21 f
or more
details.

Click on “SCADA” under the “Type” column on the Services screen to view
the SCADA Details screen (Figure 3.20). This menu gives you access to the
configuration parameters described in the paragraphs below.

Figure 3.20

SCADA Details Screen

Message Size

Maximum number of characters to buffer before sending a frame.

Values: 0

1024

Default: 256

Idle Character Delay

Maximum number of idle character time to wait before sending a frame.

Values: 0

65535

Default: 10

Input Terminator

Decimal value of the character that terminates a message before sending a
frame.

Values: 0

255

Default: 0

Data Direction

Data direction that the port will support. If set to “Input,” the port will only
accept incoming data and will not transmit data. If set to “Output,” the port
will ignore any incoming data. If set to “Both,” the port will process all data.

Values: Input, Output, Both
Default: Both