Measurement Computing Personal488 rev.3.0 For DOS & Windows 3.Xi User Manual
Page 68

II. SOFTWARE GUIDES - 8. Driver488/DRV
8D. Getting Started
Personal488 User’s Manual, Rev. 3.0
II-53
Next, take a reading from IEEE 488 bus device
16
:
C:\> ECHO ENTER 16> IEEE
C:\> TYPE IEEE
NDCV=035.679E-3
Now, if an IEEE 488 bus device name has been defined using the
INSTALL
program, that name can be
used to refer to the bus device. For example, assume that a Keithley Instruments Model 195 digital
multimeter has been given the name
K195
. The meter could be reset to its power-on conditions with a
CLEAR
command:
C:\> ECHO CLEAR K195> IEEE
To program the 195 for the 2 VDC range, send it the
R3F0X
command:
C:\> ECHO OUTPUT K195;R3F0X> IEEE
This could also be achieved by sending the command directly to the device:
C:\> ECHO R3F0X> K195
To check the status of the 195, use the
SERIAL POLL,
or
SPOLL
command:
C:\> ECHO SPOLL K195> IEEE
C:\> TYPE IEEE
To display a reading from the 195, use the
ENTER
command:
C:\> ECHO ENTER K195> IEEE
C:\> TYPE IEEE
To view continuous readings from the 195, read directly from the
K195
device:
C:\> TYPE K195
This causes readings to be taken from the 195 and displayed until
is typed. Note that
may halt Driver488/DRV in the middle of a transaction, causing the first attempt at
another command to give a
SEQUENCE ERROR
. If this should occur, simply retry the last command.
It is also possible to save the bus device data into a file:
C:\> ECHO ENTER K195> IEEE
C:\> TYPE IEEE> DATA
C:\> ECHO ENTER FREQ> IEEE
C:\> TYPE IEEE>> DATA
The first two commands create a file named
DATA
that holds a reading from the 195. The next two
commands append a reading from the device
FREQ
to the data file. Note the use of the
>>
to indicate
append.
Indicator
Driver488/DRV Status
C
It is in the Controller state.
S
It is the System Controller.
21
The value of its IEEE 488 bus address.
1
An Address Change has occurred.
I
It is idle (neither a talker nor a listener).
0
There is no
ByteIn
available.
0
It is not ready to send a
ByteOut
.
0
Service Request (
SRQ
) is not asserted.
000
There is no outstanding error.
T0
It has not received a bus device
TRIGGER
command (only applicable in the Peripheral
mode).
C0
It has not received a
CLEAR
command (only applicable in the Peripheral mode).
P0
No
CONTINUE
transfer is in progress.
OK
The error message is “OK”.