33 ~aa5n – Measurement Computing CB-COM-7021 User Manual
Page 67

67
CB-7021, CB-7022, CB-7024 User’s Manual
2.33 ~AA5N
Description:
Set Safe Value of Channel N
Note
: The command is for CB-7022 and CB-7024 only.
Command:
~AA5N[CHK](cr)
~
Delimiter character
AA
Address of setting module (00 to FF)
5
Command to store current output as Safe Value
N
Channel to set (0 to 1 for CB-7022, 0 to 3 for CB-7024)
Response:
Valid Command:
!AA[CHK](cr)
Invalid Command:
?AA[CHK](cr)
Syntax or communication error may not get a response.
!
Delimiter for valid command
?
Delimiter for invalid command
AA
Address of response module (00 to FF)
Example for CB-7024:
Command: #010+05.000
Receive: !01
Output address 01 channel 0 value +5.0, returns successful.
Command: ~0150
Receive: !01
Set address 01 channel 0 Safe Value, returns successful.
Related Command
:
Sec. 2.25,
~**; Sec. 2.26, ~AA0; Sec. 2.27, ~AA1; Sec. 2.28, ~AA2;
Sec. 2.29,
~AA3EVV; Sec. 2.31, ~AA4N
Related Topic
:
Sec. 3.2,
Module Status; Sec. 3.3, Dual Watchdog Operation