1 %aannttccff – Measurement Computing CB-COM-7021 User Manual
Page 29

29
CB-7021, CB-7022, CB-7024 User’s Manual
2.1 %AANNTTCCFF
Description:
Set module Configuration
Syntax:
%AANNTTCCFF[CHK](cr)
%
Delimiter character
AA
Address of setting module (00 to FF)
NN
New address for setting module (00 to FF)
TT
New type for setting module (Ref Sec. 1.10)
CC
New baud rate for setting module (Ref Sec. 1.10)
FF
New data format for setting module (Ref Sec. 1.10)
When changing the baud rate or checksum, short the
INIT* pin to ground.
Response:
Valid Command:
!AA[CHK](cr)
Invalid Command:
?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
!
Delimiter for valid command
?
Delimiter for invalid command. While changing baud rate
or checksum setting without shorting INIT* to ground, the
module will returns an invalid command message.
AA
Address of response module (00 to FF)
Example:
Command: %0102300600
Receive: !02
Change address from 01 to 02, returns successful.
Related Command
:
Sec. 2.2
$AA2
Related Topics
:
Sec. 1.10
Configuration Tables, Sec. 3.1 INIT* pin Operation