3 $aa5 – Measurement Computing CB-COM-7021 User Manual
Page 31

31
CB-7021, CB-7022, CB-7024 User’s Manual
2.3 $AA5
Description:
Read Reset Status
Command:
$AA5[CHK](cr)
$
Delimiter character
AA
Address of reading module (00 to FF)
5
Command for reading reset status
Response:
Valid Command:
!AAS[CHK](cr)
Invalid Command:
?AA[CHK](cr)
Syntax or communication error may get no
response.
!
Delimiter for valid command
?
Delimiter for invalid command
AA
Address of response module (00 to FF)
S
Reset status, 1 = the module is been reset; 0 = the
module is not been reset.
Example:
Command: $015
Receive: !011
Read address 01 reset status, returns first read.
Command: $015
Receive: !010
Read address 01 reset status, returns no reset occurred.