CB-7021, CB-7022, CB-7024 User’s Manual
CB-7024 Current Output Calibration Sequence:
1.
Connect meter to module’s voltage output channel 0.
2.
Warm-Up for 30 minutes.
3.
Setting type to 33. (
−
10 to 10V)
-> Refer Sec. 2.1.
4.
Output
−
10V.
-> Refer Sec. 2.15.
5.
Check the meter and trim the output for
−
10V match by using trim command.
-> Refer Sec. 2.18.
6.
Perform
−
10V Calibration Command. -> Refer Sec. 2.16.
7.
Program output for 10V.
Refer Sec. 2.15.
8.
Check the meter and trim the output for
10V match by using trim command.->
Refer
Sec. 2.18.
9.
Perform 10V Calibration Command.
-> Refer Sec. 2.17.
10. Repeat 1 to 9 for channel 1, 2 and 3.