1.5 Jumper Setting

Jumper-select the current output power supply of CB-7021/21P:
1.

Select internal power of module. The default setting can drive

a load of up to 500 ohms.

2.

Select external power of module: can drive larger load. With

24V power, it can drive 1050 ohms.

Jumper select the current output power supply of CB-7022:
1.

JP1 for channel 0 setting, and JP2 for channel 1 setting.

2.

Select internal power: 500 ohms load max.

3.

External power: 1050 ohms with external +24VDC power.

1.6 Wire Connection

CB-7021/21P/22

Voltage Output Wire Connection