3 specifications – Measurement Computing CB-COM-7021 User Manual
Page 10

10
CB-7021, CB-7022, CB-7024 User’s Manual
1.3 Specifications
CB-7021
Analog Output
Output Channel: 1
Output Type: mA, V
Accuracy: ±0.1% of FSR
Resolution: ±0.02% of FSR
Readback Accuracy: ±1% of
FSR
Zero Drift:
Voltage output: ±30µV/°C
Current output: ±0.2µA/°C
Span Temperature Coefficient:
±25ppm/°C
Programmable Output Slope:
0.125 to 1024 mA/Second
0.0625 to 512 V/Second
Voltage Output: @ 10 mA max.
Current Load Resistance:
Internal power: 500 ohms
External 24V: 1050 ohms
Isolation: 3000VDC
Power Supply
Input: +10 to +30VDC
Consumption: 1.8 W.
CB-7021P
Analog Output
Output Channel: 1
Output Type: mA, V
Accuracy: ±0.02% of FSR
Resolution: ±0.002% of FSR
Readback Accuracy: ±1% of
FSR
Zero Drift:
Voltage output: ±10µV/°C
Current output: ±0.2µA/°C
Span Temperature Coefficient:
±5ppm/°C
Programmable Output Slope:
0.125 to 1024 mA/Second
0.0625 to 512 V/Second
Voltage Output: @ 10 mA max.
Current Load Resistance:
Internal power: 500 ohms
External 24V: 1050 ohms
Isolation: 3000VDC
Power Supply
Input: +10 to +30VDC
Consumption: 1.8 W.