beautypg.com

28 ~aa2 – Measurement Computing CB-COM-7021 User Manual

Page 61

background image

61

CB-7021, CB-7022, CB-7024 User’s Manual

2.28 ~AA2

Description:

Read Host Watchdog Timeout Interval

Command:

~AA2[CHK](cr)

~

Delimiter character

AA

Address of reading module (00 to FF)

2

Command for reading host watchdog timeout interval

Response:

Valid Command:

!AAEVV[CHK](cr)

Invalid Command:

?AA[CHK](cr)

Syntax or communication error may not get a
response.

!

Delimiter for valid command

?

Delimiter for invalid command

AA

Address of response module (00 to FF)

E

1=Enable/0=Disable host watchdog

VV

Timeout interval in hexadecimal format, count for 0.1

second, 01 = 0.1 second and FF = 25.5 seconds

Example:
Command: ~012

Receive: !010FF

Read address 01 host watchdog timeout interval, returns host

watchdog disable, and time interval is 25.5 seconds.

Related Command

:

Sec. 2.25,

~**; Sec. 2.26, ~AA0; Sec. 2.27, ~AA1; Sec. 2.29,

~AA3EVV; Sec. 2.30, ~AA4; Sec. 2.31, ~AA4N; Sec. 2.32, ~AA5;

Sec. 2.33,

~AA5N

Related Topic

:

Sec. 3.2,

Module Status; Sec. 3.3, Dual Watchdog Operation

This manual is related to the following products: