16 $aa0n – Measurement Computing CB-COM-7021 User Manual
Page 47

47
CB-7021, CB-7022, CB-7024 User’s Manual
2.16 $AA0N
Description:
CB-7022: Perform 4 mA Calibration for Channel N
CB-7024: Perform 0 mA/-10V Calibration for Channel N
Note
: The command is for CB-7022 and CB-7024 only.
Syntax:
$AA0N[CHK](cr)
$
Delimiter character
AA
Address of setting module (00 to FF)
0
command for doing 4 mA (or 0 mA/-10V) calibration
N
channel to calibrate (0 to 1 for CB-7022, 0 to 3 for CB-
7024)
Response:
Valid Command:
!AA[CHK](cr)
Invalid Command:
?AA[CHK](cr)
Syntax error or communication error may get no
response.
!
Delimiter for valid command
?
Delimiter for invalid command
AA
Address of response module (00 to FF)
Example:
Command: $0101
Receive: !01
Perform Address 01 channel 1 calibration (4 mA for CB-7022,
0 mA or -10.0V for CB-7024), returns successful.
Related Command
:
Sec. 2.17
$AA1N, Sec. 2.18 $AA3NVV
Related Topics
:
Sec. 1.9
Calibration