19 $aa4n – Measurement Computing CB-COM-7021 User Manual
Page 50

50
CB-7021, CB-7022, CB-7024 User’s Manual
2.19 $AA4N
Description:
Set PowerOn Value for Channel N
Note
: The command is for CB-7022 and CB-7024 only.
Syntax:
$AA4N[CHK](cr)
$
Delimiter character
AA
Address of setting module (00 to FF)
4
Command for setting PowerOn Value, store the current
output value as PowerOn Value.
N
Channel to set (0 to 1 for CB-7022, 0 to 3 for CB-7024)
Response:
Valid Command:
!AA[CHK](cr)
Invalid Command:
?AA[CHK](cr)
Syntax error or communication error may not get
response.
!
Delimiter for valid command
?
Delimiter for invalid command
AA
Address of response module (00 to FF)
Example for CB-7024:
Command: #012+00.000
Receive: >
Set address 01 channel 2 output 0.0, returns successful.
Command: $0142
Receive: !01
Set address 01 channel 2 PowerOn Value, returns successful.
The Power-On Value of channel 2 is set to 0.0 now.
Related Command
:
Sec. 2.15
#AAN(Data), Sec. 2.21 $AA7N
Related Topics
:
Sec. 1.10,
Configuration Tables; Sec. 3.5, Analog Output