24 $aa9nts – Measurement Computing CB-COM-7021 User Manual
Page 57

57
CB-7021, CB-7022, CB-7024 User’s Manual
2.24 $AA9NTS
Description:
Set DA Configuration of Channel N
Note
: The command is for CB-7022 only.
Syntax:
$AA9NTS[CHK](cr)
$
Delimiter character
AA
Address of reading module (00 to FF)
9
Command for setting DA configuration
N
Channel to set DA configuration (0 to 1)
T
Analog output type. Refer Sec. 1.10 for type select
S
Analog output slew rate. Refer Sec. 1.10 for slew rate
select
Response:
Valid Command:
!AA[CHK](cr)
Invalid Command:
?AA[CHK](cr)
Syntax error or communication error may not get
a response.
!
Delimiter for valid command
?
Delimiter for invalid command
AA
Address of response module (00 to FF)
Example:
Command: $019121
Receive: !01
Set address 01 channel 1 DA configuration: 0 to 10V output
and slew rate 0.625V/Second, returns successful.
Related Command
:
Sec. 2.23
$AA9N