Measurement Computing CB-COM-7021 User Manual
Page 36

36
CB-7021, CB-7022, CB-7024 User’s Manual
range, and the output is set to 20.0 mA.
Command: $022
Receive: !02300601
Read address 02 configuration, returns output type 0 to 20
mA, percent of span format, output change immediate.
Command: #02+050.00
Receive: >
Output address 02 value 50% (=10 mA), returns successful.
Command: $032
Receive: !02300602
Read address 03 configuration, returns output type 0 to 20
mA, hexadecimal format, output change immediate.
Command: #03800
Receive: >
Output address 03 value 0x800 (=10 mA), returns successful.
Related Command
:
Sec. 2.1
%AANNTTCCFF, Sec. 2.2 $AA2
Related Topics
:
Sec. 1.10
Configuration Tables, Sec. 3.5 Analog Output
This manual is related to the following products: