beautypg.com

Measurement Computing CB-COM-7021 User Manual

Page 36

background image

36

CB-7021, CB-7022, CB-7024 User’s Manual

range, and the output is set to 20.0 mA.

Command: $022

Receive: !02300601

Read address 02 configuration, returns output type 0 to 20

mA, percent of span format, output change immediate.

Command: #02+050.00

Receive: >

Output address 02 value 50% (=10 mA), returns successful.

Command: $032

Receive: !02300602

Read address 03 configuration, returns output type 0 to 20

mA, hexadecimal format, output change immediate.

Command: #03800

Receive: >

Output address 03 value 0x800 (=10 mA), returns successful.