beautypg.com

Measurement Computing CB-COM-7021 User Manual

Page 46

background image

46

CB-7021, CB-7022, CB-7024 User’s Manual

Read address 01, channel 0 DA config., returns 4 to 20 mA.

output and change immediate.

Command: #01005.000

Receive: >

Output address 01 channel 0 value 5.0 mA, returns success-

ful.

Command: #01025.000

Receive: ?01

Output address 01 channel 0 value 25 mA, returns out of range,

and the output of channel 0 is set to the 20.0 mA

Example for CB-7024:
Command: $012

Receive: !01300600

Read address 01 configuration, returns type 0 to 20mA, 9600

bps and engineer unit format, output change immediate.

Command: #010+05.000

Receive: >

Output address 01 channel 0 value 5.0 mA, returns success-

ful.

Command: #010+25.000

Receive: ?01

Output address 01 channel 0 value 25.0 mA, returns the value

is out of range, and the output of channel 0 is set to the 20.0
mA.

Related Command

:

Sec. 2.1

%AANNTTCCFF, Sec. 2.2 $AA2

Related Topics

:

Sec. 1.10

Configuration Tables, Sec. 3.5 Analog Output

This manual is related to the following products: