32 ~aa5 – Measurement Computing CB-COM-7021 User Manual
Page 66

66
CB-7021, CB-7022, CB-7024 User’s Manual
2.32 ~AA5
Description:
Set Safe Value.
Note
: The command is for CB-7021/21P only.
Command:
~AA5[CHK](cr)
~
Delimiter character
AA
Address of setting module (00 to FF)
5
Command to store current output as Safe Value
Response:
Valid Command:
!AA[CHK](cr)
Invalid Command:
?AA[CHK](cr)
Syntax or communication error may not get a response.
!
Delimiter for valid command
?
Delimiter for invalid command
AA
Address of response module (00 to FF)
Example:
Command: #0100.000
Receive: !01
Output address 01 value 0.0, returns successful.
Command: ~015
Receive: !01
Set address 01 Safe Value, returns successful.
Related Command
:
Sec. 2.25,
~**; Sec. 2.26, ~AA0; Sec. 2.27, ~AA1; Sec. 2.28, ~AA2;
Sec. 2.29,
~AA3EVV; Sec. 2.30, ~AA4
Related Topic
:
Sec. 3.2,
Module Status; Sec. 3.3, Dual Watchdog Operation