beautypg.com

1 $aa7n – Measurement Computing CB-COM-7021 User Manual

Page 52

background image

52

CB-7021, CB-7022, CB-7024 User’s Manual

2.21.1 $AA7N

Description:

Perform 10V Calibration for Channel N

Note

: The command is for CB-7022 only.

Syntax:

$AA7N[CHK](cr)

$

Delimiter character

AA

Address of reading module (00 to FF)

7

command for performing 10V calibration

N

channel to calibrate (0 to 1)

Response:

Valid Command:

!AA[CHK](cr)

Invalid Command:

?AA[CHK](cr)

Syntax error or communication error may get no re-
sponse.

!

Delimiter for valid command

?

Delimiter for invalid command

AA

Address of response module (00 to FF)

Example:
Command: $0170

Receive: !01

Perform address 01 channel 0 10V calibration, returns

successful.

Related Command

:

Sec. 2.16,

$AA0N, Sec. 2.17, $AA1N

Related Topics

:

Sec. 1.9,

Calibration

This manual is related to the following products: