beautypg.com

6 ~aao(data) – Measurement Computing CB-COM-7021 User Manual

Page 34

background image

34

CB-7021, CB-7022, CB-7024 User’s Manual

2.6 ~AAO(Data)

Description:

Set Module Name

Syntax:

~AAO(Data)[CHK](cr)

~

Delimiter character

AA

Address of setting module (00 to FF)

O

Command for setting module name

(Data)

New name for module, max 6 characters

Response:

Valid Command:

!AA[CHK](cr)

Invalid Command:

?AA[CHK](cr)

Syntax error or communication error may get no
response.

!

Delimiter for valid command

?

Delimiter for invalid command

AA

Address of response module (00 to FF)

Example:
Command: ~01O7021

Receive: !01

Set address 01 module name to 7021, returns successfulful.

Command: $01M

Receive: !017021

Read address 01 module name, returns 7021.

Related Command

:

Sec. 2.5

$AAM