30 ~aa4 – Measurement Computing CB-COM-7021 User Manual
Page 64

64
CB-7021, CB-7022, CB-7024 User’s Manual
2.30 ~AA4
Description:
Read Safe Value.
Note
: The command is for CB-7021/21P only.
Command:
~AA4[CHK](cr)
~
Delimiter character
AA
Address of reading module (00 to FF)
4
Command for read Safe Value
Response:
Valid Command:
!AA(Data)[CHK](cr)
Invalid Command:
?AA[CHK](cr)
Syntax error or communication error may not get a
response.
!
Delimiter for valid command
?
Delimiter for invalid command
AA
Address of response module (00 to FF)
(Data)
Safe Value of module. Refer Sec. 1.10 for data format
Example:
Command: ~014
Receive: !0105.000
Read address 01 Safe Value, returns 5.0.
Related Command
:
Sec. 2.25,
~**; Sec. 2.26, ~AA0; Sec. 2.27, ~AA1; Sec. 2.28, ~AA2;
Sec. 2.29,
~AA3EVV; Sec. 2.32, ~AA5
Related Topic
:
Sec. 3.2,
Module Status; Sec. 3.3, Dual Watchdog Operation