64

CB-7021, CB-7022, CB-7024 User’s Manual

2.30 ~AA4

Description:

Read Safe Value.

Note

: The command is for CB-7021/21P only.

Command:

~AA4[CHK](cr)

~

Delimiter character

AA

Address of reading module (00 to FF)

4

Command for read Safe Value

Response:

Valid Command:

!AA(Data)[CHK](cr)

Invalid Command:

?AA[CHK](cr)

Syntax error or communication error may not get a
response.

!

Delimiter for valid command

?

Delimiter for invalid command

AA

Address of response module (00 to FF)

(Data)

Safe Value of module. Refer Sec. 1.10 for data format

Example:
Command: ~014

Receive: !0105.000

Read address 01 Safe Value, returns 5.0.

Related Command

:

Sec. 2.25,

~**; Sec. 2.26, ~AA0; Sec. 2.27, ~AA1; Sec. 2.28, ~AA2;

Sec. 2.29,

~AA3EVV; Sec. 2.32, ~AA5

Related Topic

:

Sec. 3.2,

Module Status; Sec. 3.3, Dual Watchdog Operation

This manual is related to the following products: