beautypg.com

23 $aa9n – Measurement Computing CB-COM-7021 User Manual

Page 56

background image

56

CB-7021, CB-7022, CB-7024 User’s Manual

2.23 $AA9N

Description:

Read DA Configuration of Channel N

Note

: The command is for CB-7022 only.

Syntax:

$AA9N[CHK](cr)

$

Delimiter character

AA

Address of reading module (00 to FF)

9

Command for reading DA configuration

N

Channel to read DA configuration (0 to 1)

Response:

Valid Command:

!AATS[CHK](cr)

Invalid Command:

?AA[CHK](cr)

Syntax error or communication error may not get
a response.

!

Delimiter for valid command

?

Delimiter for invalid command

AA

Address of response module (00 to FF)

T

Analog output type. See Sec. 1.10 for format.

S

Analog output slew rate. See Sec. 1.10 for format.

Example:
Command: $0190

Receive: !0110

Read address 01 channel 0 DA configuration, returns 4 to 20

mA output and change immediate.

Related Command

:

Sec. 2.24,

$AA9NTS

This manual is related to the following products: