23 $aa9n – Measurement Computing CB-COM-7021 User Manual
Page 56

56
CB-7021, CB-7022, CB-7024 User’s Manual
2.23 $AA9N
Description:
Read DA Configuration of Channel N
Note
: The command is for CB-7022 only.
Syntax:
$AA9N[CHK](cr)
$
Delimiter character
AA
Address of reading module (00 to FF)
9
Command for reading DA configuration
N
Channel to read DA configuration (0 to 1)
Response:
Valid Command:
!AATS[CHK](cr)
Invalid Command:
?AA[CHK](cr)
Syntax error or communication error may not get
a response.
!
Delimiter for valid command
?
Delimiter for invalid command
AA
Address of response module (00 to FF)
T
Analog output type. See Sec. 1.10 for format.
S
Analog output slew rate. See Sec. 1.10 for format.
Example:
Command: $0190
Receive: !0110
Read address 01 channel 0 DA configuration, returns 4 to 20
mA output and change immediate.
Related Command
:
Sec. 2.24,
$AA9NTS