2.20 $AA6N

Description:

Last Value of Channel N Readback

Note

: The command is for CB-7022 and CB-7024 only.

Syntax:

$AA6N[CHK](cr)

$

Delimiter character

AA

Address of reading module (00 to FF)

6

Command for reading last output command value

N

Channel to readback (0 to 1 for CB-7022, 0 to 3 for CB-

7024)

Response:

Valid Command:

!AA(Data)[CHK](cr)

Invalid Command:

?AA[CHK](cr)

Syntax or comm. error may not get response.

!

Delimiter for valid command

?

Delimiter for invalid command

AA

Address of response module (00 to FF)

(Data)

Last output command value. See Sec. 1.9 for format.

Example for CB-7024:
Command: #013+10.000

Receive: !01

Set address 01 channel 3 output 10.0, returns successful.

Command: $0163

Receive: !01+10.000

Read address 01 channel 3 last output command value, re-

turns 10.000.