beautypg.com

15 #aan(data) – Measurement Computing CB-COM-7021 User Manual

Page 45

background image

45

CB-7021, CB-7022, CB-7024 User’s Manual

2.15 #AAN(Data)

Description:

Output Analog Value for Channel N

Note

: The command is for CB-7022 and CB-7024 only.

Syntax:

#AAN(Data)[CHK](cr)

#

Delimiter character

AA

Address of output module (00 to FF)

N

Output channel (0 to 1 for CB-7022, 0 to 3 for CB-

7024)

(Data)

Analog output value, reference Sec. 1.10 for its format.

Response:

Valid Command:

>[CHK](cr)

Invalid Command:

?AA[CHK](cr)

Ignore Command:

![CHK](cr)

Syntax error or communication error may get no
response.

>

Delimiter for valid command

?

Delimiter for invalid command. When the (Data) is out

of range, and the output will go to the closest value in the
module’s range.

!

Delimiter for the module’s host watchdog status is set,

and the output command will be ignored.

AA

Address of response module (00 to FF)

Example for CB-7022:
Command: $012

Receive: !013F0600

Read address 01 configuration, returns multichannel output,

9600 bps and engineering unit format.

Command: $0190

Receive: !0110

This manual is related to the following products: