2.8 $AA0

Description:

Perform 4 mA Calibration

Note

: The command is for CB-7021/21P only.

Syntax:

$AA0[CHK](cr)

$

Delimiter character

AA

Address of setting module (00 to FF)

0

command for performing 4 mA calibration

Response:

Valid Command:

!AA[CHK](cr)

Invalid Command:

?AA[CHK](cr)

Syntax error or communication error may get no re-
sponse.

!

Delimiter for valid command

?

Delimiter for invalid command

AA

Address of response module (00 to FF)

Example:
Command: $010

Receive: !01

Perform address 01 4 mA calibration, returns successful.

Related Command

:

Sec. 2.9

$AA1, Sec. 2.10 $AA3VV

Related Topics

:

Sec. 1.9

Calibration