beautypg.com

11 $aa4 – Measurement Computing CB-COM-7021 User Manual

Page 40

background image

40

CB-7021, CB-7022, CB-7024 User’s Manual

2.11 $AA4

Description:

Set PowerOn Value

Note

: The command is for CB-7021/21P only.

Syntax:

$AA4[CHK](cr)

$

Delimiter character

AA

Address of setting module (00 to FF)

4

Command for setting PowerOn Value. Store the current

output value as PowerOn Value.

Response:

Valid Command:

!AA[CHK](cr)

Invalid Command:

?AA[CHK](cr)

Syntax error or communication error may get no re-
sponse.

!

Delimiter for valid command

?

Delimiter for invalid command

AA

Address of response module (00 to FF)

Example:
Command: #0100.000

Receive: >

Set address 01 output 0.0 mA, returns successful.

Command: $014

Receive: !01

Set address 01 PowerOn V alue, returns successful. The

module 01 will go to 0.0 mA with module power on.

Related Command

:

Sec. 2.7

#AA(Data)

Related Topics

:

Sec. 3.5

Analog Output

This manual is related to the following products: