2 digital outputs m12 for ep2028-0032, 3 digital outputs sub-d 25, 16 channels, Actuator connection – BECKHOFF EP2xxx User Manual
Page 96

Mounting and cabling
Fig. 89: Digital outputs, M8 and M12
The outputs are shortcircuit safe and protected against inverse connection.
The outputs indicate their status through light emitting diodes.
3.6.2
Digital outputs M12 for EP20280032
The digital outputs / actuators are connected via M12 sockets.
Pin 2 and 4 of channel 0 and 1, channel 2 and 3, channel 4 and 5 as well as channel 6 and 7 are connected.
Therefore also actuators witch needs 2 outputs can be connected via one M12 cable.
Fig. 90: Digital outputs M12 for EP20280032
The state of the signals is indicated by light emitting diodes.
3.6.3
Digital outputs SubD 25, 16 channels
The EP2816 digital output module transmits the binary control signals from the automation unit on to the
actuators at the process level.
The 16 outputs deliver load currents of up to 0.5 A, although the total current from all the outputs must not
exceed 4 A.
The signal connection is made through a 25pin subD socket.
The outputs are shortcircuit proof and protected against inverse connection.
EP2xxx
96
Version 2.1.0