6 ep2316-0008 - configuration, Configuration – BECKHOFF EP2xxx User Manual
Page 32

Product overview
Fig. 20: EP23160008, DIG Outputs Device
Set safe state
Sets the module to safe state.
Reset outputs
Resets bits „Error channel X“ of the module. The outputs are activated again.
2.7.6
EP23160008 Configuration
A number of parameterizations can be carried out for the EP23160003, EP23160008, 28160008 and
28160010 modules on the C0E Online tab in the TwinCAT System Manager.
The description of the parameterizations is done with the help of EP23160008 but is suitable for all this
modules.
Definitions for the behavior of the outputs in case of network failure
With bit 8000:0n (Safe State Active) you can specify that channel n should adopt a specified value (Safe
State Value) if the network communication is interrupted or not.
With bit 8001:0n (Safe State Value) you define this specific value for channel n.
Note
Safe State Value at network start up
The network transfers output process data only at the network states BOOT und Opera
tional (OP). Also at the network states INIT, PreOperational (PREOP) and SaveOpera
tional (SAFEOP) passed trough during network start up no output process data is transmit
ted. If Safe State is activated for an output, this output adopts the specified value also dur
ing network start up.
8000:0 DIG Safe state active Ch.1
Note
Observe the maximum shortcircuit current!
When dimensioning the power supply unit and choosing the fuses, observe that the short
circuit current is approximately 1.7 A.
EP2xxx
32
Version 2.1.0