2 ep2339-0022 - introduction, Ep2339‐0022 – BECKHOFF EP2xxx User Manual
Page 41

Product overview
Attention
For switch off in the event of a fault, do no external sensor power supply
If the design of your installation is such that the power supply voltage Up is switched off in
the event of a fault, you must not power the connected sensors externally, but only through
the EP23390021! Otherwise, when the Up energy is switched off, the EP23390021 can
continue to draw energy from the external sensor power supply, and the outputs will not be
switched off!
Quick links
Installation
2.9.2
EP23390022 Introduction
Fig. 27: EP23390022
16 digital in or outputs, 24 V
DC
The EP23390022 EtherCAT Box has 16 digital channels, each of which can optionally be operated as an
input or as an output. A configuration if a channel should be used as input or as an output is not necessary;
the input circuit is internally connected to the output driver, so a set output is displayed automatically to the
input process image.
The outputs handle load currents of up to 0.5 A, are shortcircuit proof and protected against inverse polarity.
The filter constant of the inputs is 3 ms.
The state of each signal is indicated by means of light emitting diodes. The signals are connected via M12
connectors.
EP2xxx
41
Version 2.1.0