3 power cables, 4 power cable conductor losses – BECKHOFF EP2xxx User Manual
Page 90

Mounting and cabling
3.3.3
Power cables
Ordering data
Order designation
Power lead
Screwin
connector
Contacts
Crosssection Length
ZK202032000020
Straight socket, open end
M8
4pin
0.34 mm
2
2.00 m
ZK202032000050
5.00 m
ZK202032000100
10.00 m
ZK202034000020
Angled socket, open end
2.00 m
ZK202034000050
5.00 m
ZK202034000100
10.00 m
ZK202031320001
Straight socket, straight
socket
0.15 m
ZK202031320005
0.50 m
ZK202031320010
1.00 m
ZK202031320020
2.00 m
ZK202031320050
5.00 m
ZK202033340001
Angled socket, angled
socket
0.15 m
ZK202033340005
0.50 m
ZK202033340010
1.00 m
ZK202033340020
2.00 m
ZK202033340050
5.00 m
Further available power cables may be found in the Beckhoff catalog or on our internet pages (
www.beckhoff.com).
Technical data
Technical data
Rated voltage according to IEC60 6641
60 V
AC
/ 75 V
DC
Contamination level according to IEC 60 6641
3/2
Insulation resistance IEC 60 5122
>10
9
W
Current carrying capacity according to IEC 605123
4 A
Volume resistance according to IEC 605122
< 5 mW
Protection class according to IEC 60529
IP65/66/67, when screwed together
Ambient temperature
30°C to +80°C
3.3.4
Power cable conductor losses
The ZK2020xxxxyyyy power cables should not exceed the total length of 15 m at 4 A (with continuation).
When planning the cabling, note that at 24 V nominal voltage, the functionality of the module can no longer
be assured if the voltage drop reaches 6 V. Variations in the output voltage from the power supply unit must
also be taken into account.
EP2xxx
90
Version 2.1.0